Issue
"Configured" status is not displayed (checked or unchecked) in TGML for Cubicle 5 to Cubicle 16 for SMD (Switchgear Monitoring Device)

Product Line
PO2021 PSO2020 R2 CU1
Environment
PO2021 / PSO2020R2CU1 with webHMI application having SMD devices
Solution
"Configured" status is not displayed (checked or unchecked) in TGML for Cubicle 5 to Cubicle 16 for SMD (Switchgear Monitoring Device)
Product Line
PO2021 PSO2020 R2 CU1
Environment
PO2021 / PSO2020R2CU1 with webHMI application having SMD devices
Solution
- Close any open webHMI application in browser
- Stop IIS from IIS Manager
- Navigate to C:\ProgramData\Schneider Electric\Power SCADA Operation\v2021\User\PLS_Include\TGML\Templates\Thermal
- Take backup of "Thermal" Folder in v2021 folder and its sub-folders (C:\ProgramData\Schneider Electric\Power SCADA Operation\v2021)
- Replace the attached (Related) TGML files in Thermal folder normally located at C:\ProgramData\Schneider Electric\Power SCADA Operation\v2021\User\PLS_Include\TGML\Templates\Thermal
- If your installation location is different, please make sure you replace these files in Power SCADA Operation\v2021\User\PLS_Include\TGML\Templates\Thermal
- Start IIS Manager
- Open the TGML for SMD and verify the "Configured" Status visible for all Cubicles.
- If not able to view updated TGMLs , perform iisreset using Command Prompt (Required Administrator privileges).
Udgivet til: Schneider Electric Danmark


Brug for hjælp?
Produktvælger
Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.
Få et tilbud
Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.
Find forhandler
Find den nærmeste Schneider Electric-distributør.
Hjælpecenter
Find supportressourcer til alle dine behov på ét sted.