Issue:
Looking for an internal system variable that will reveal the status of the Ethernet port of an HMIST6
Product Line:
Harmony HMI, HMIST6, HMISTM6, EcoStruxure Operator Terminal Expert
Resolution:
Currently in EcoStruxure Operator Terminal Expert V3.2 SP1, there is no way to determine the status of the Ethernet port by the means of a built-in Internal System Variable.
As a workaround, we could monitor the Quality property of an External Variable. Here are the different states that the Quality property could be in:
Here is an example script that will write the Quality property to a variable named "StatusVar". Note Var1 is our external variable.
Looking for an internal system variable that will reveal the status of the Ethernet port of an HMIST6
Product Line:
Harmony HMI, HMIST6, HMISTM6, EcoStruxure Operator Terminal Expert
Resolution:
Currently in EcoStruxure Operator Terminal Expert V3.2 SP1, there is no way to determine the status of the Ethernet port by the means of a built-in Internal System Variable.
As a workaround, we could monitor the Quality property of an External Variable. Here are the different states that the Quality property could be in:
Value | Description |
0, 4 | Access to device address and device address value is normal. |
1, 3, 5, 7 | Cannot access the device address. |
8, 12 | Device address value is invalid. |
9, 13, 15 | You cannot access the device address. Also, the device address value can be invalid. |
2, 6, 10, 11, 14 | Not in use |
Here is an example script that will write the Quality property to a variable named "StatusVar". Note Var1 is our external variable.
Udgivet til: Schneider Electric Danmark


Brug for hjælp?
Produktvælger
Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.
Få et tilbud
Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.
Find forhandler
Find den nærmeste Schneider Electric-distributør.
Hjælpecenter
Find supportressourcer til alle dine behov på ét sted.