Setup the ATV340 Drives Ethernet IP address using the optional remote keypad display.
Issue:
ATV340 programming setting up the Ethernet IP address using optional HMI.
Product Line:
ATV340 with optional keypad VW3A1113 or VW3A1111.
Environment:
All
Cause:
Programming setup Ethernet IP address
Resolution:
This programming example is if you use one of the optional keypad to program your drive.
[Communication] -[Comm parameters]- [Embd Eth Config]
-[Embd Eth Config] EtE- Menu
PAn= Add a Device name
iNOO= IP mode set to NAnu or Fixed
iCO= IP Address (IC01, IC02, IC03, IC04).
iNO= Subnet mask (IM01, IM02, IM03, IM04).
iGO= Gateway address (IG01, IG02, IG03, IG04).
After setting up your IP address and subnet address etc you will need to power cycle the drive.