What's new with M580 cybersecurity PLC SV4.01 - Common questions

Can I have "gray" products with PV < 25
Gray CPUs means necessarily PV>=25 ( except for satefy modules which will stay red)..

Are the "white" CPUs going to phased out and only "gray" CPUs will be sold? When will this transition happen?
Yes, white CPUs are phased out. Transition has already started.

Can my white CPU be certified 62443-4-2 later on ?
No. This certification requires electronic components which are not implemented on products with PV<25, so, white CPU cannot be certified.

Can I move the SD card from V2.xx to V4.xx CPU, and start in RUN mode without connecting Control Expert and downloading the application?
Yes it is feasible.

Is-it possible to upgrade directly an existing V2.xx version to a V4.xx?
It will be the same process as for V3.20, you will first have to upgrade to V3.99. A dedicated note explaining the upgrade process is attached to this FAQ.

Schneider Electric Danmark

Bilag
EIO0000004716.00.pdf [317.3 KB]
Se mere
Område:
Se mere
Område:

Brug for hjælp?

Brug for hjælp?

Produktvælger

Produktvælger

Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.

Få et tilbud

Få et tilbud

Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.

Find forhandler

Find forhandler

Find den nærmeste Schneider Electric-distributør.

Hjælpecenter

Hjælpecenter

Find supportressourcer til alle dine behov på ét sted.

  • Produktdokumentation
  • Download af software
  • Produktvælger
  • Udskiftning og erstatning af produkter
  • Hjælp og kontaktcenter
  • Find forhandler
  • Projektrådgivning
  • Find vores kontorer
  • Schneider Electric Community
  • Karriere
  • Virksomhedsprofil
  • Rapportér en forseelse
  • Tilgængelighed
  • Presserum
  • Investorer
  • EcoStruxure
  • Jobsøgning
  • Blog
  • Privatlivspolitik
  • Cookiemeddelelse
  • Vilkår for anvendelse
  • Rediger dine cookieindstillinger