Why can't I open my .STU file but .STA works using CE V15.0 ?

Issue

When upgrading a Control Expert project created with a version earlier than V14.1 to Control Expert V15, an issue may occur if the project contains password-protected elements.

The issue may be related to one of the following configurations:

  • Password protection is configured without a password.
  • Password protection is configured with an empty password.

These configurations are no longer allowed in Control Expert V15 and later.

Product Line

EcoStruxure Control Expert

Environment

  • Project originally created with a Control Expert version earlier than V14.1
  • Project opened or upgraded with Control Expert V15

Resolution

Two possible resolutions are currently identified:

Option 1: Upgrade Control Expert

Upgrade to Control Expert V15.1, where this issue is reported as corrected.

Option 2: Remain on Control Expert V15

If Control Expert V15 must be retained:

  1. Export the affected DFBs.
  2. Reimport the DFBs into the project.
  3. Verify that the project can then be processed without the password-related issue.

Schneider Electric Danmark

Se mere
Område:
Se mere
Område:
  • Produktdokumentation
  • Download af software
  • Produktvælger
  • Udskiftning og erstatning af produkter
  • Hjælp og kontaktcenter
  • Find forhandler
  • Projektrådgivning
  • Find vores kontorer
  • Schneider Electric Community
  • Karriere
  • Virksomhedsprofil
  • Rapportér en forseelse
  • Tilgængelighed
  • Presserum
  • Investorer
  • EcoStruxure
  • Jobsøgning
  • Blog
  • Generelle forretningsbetingelser
  • Privatlivspolitik
  • Cookiemeddelelse
  • Vilkår for anvendelse
  • Rediger dine cookieindstillinger
  • Præferencecenter