Ecostruxure Automation Expert[22.0]: Answer Timeout error

This document explains users on how to resolve the Answer timeout error when tried to deploy a Project to M580DPAC Controller.

For larger projects, User sometimes might experience "Answer Timeout error" for Deployment failure.

In such case, User needs to tune the ECORT Plugin Settings which can be accessed as shown below.

plug inanswer

The Answer timeout is 10 seconds by default and needs to be increased if Answer timeout error is appearing frequently for deployment failure. After modifying the setting, compile the project and deploy the project.