Can a PM5500 series meter have a Modbus TCP/IP and BACnet IP master connection simultaneously?

Issue
A customer needs to connect one PM5500 meter to two different sites using two different protocols.

Product Line
PM5560, PM5563

Environment

Communications

commissioning

Resolution

BACnet and Modbus are different communication protocols.

  • BACnet is a broadcasting protocol where devices continuously listen to the master. When their turn (token) comes, they respond to the master.
  • Modbus, on the other hand, is a request/reply protocol that provides services defined by function codes. These function codes are elements of the Modbus request/reply Protocol Data Unit (PDU).

The PM5500 meter can communicate with both systems simultaneously without any issues.

PM5000 series meter documentation: FA234023

Schneider Electric Danmark

Se mere
Produkt:
Se mere
Produkt:

Brug for hjælp?

Brug for hjælp?

Produktvælger

Produktvælger

Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.

Få et tilbud

Få et tilbud

Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.

Find forhandler

Find forhandler

Find den nærmeste Schneider Electric-distributør.

Hjælpecenter

Hjælpecenter

Find supportressourcer til alle dine behov på ét sted.

  • Produktdokumentation
  • Download af software
  • Produktvælger
  • Udskiftning og erstatning af produkter
  • Hjælp og kontaktcenter
  • Find forhandler
  • Projektrådgivning
  • Find vores kontorer
  • Schneider Electric Community
  • Karriere
  • Virksomhedsprofil
  • Rapportér en forseelse
  • Tilgængelighed
  • Presserum
  • Investorer
  • EcoStruxure
  • Jobsøgning
  • Blog
  • Privatlivspolitik
  • Cookiemeddelelse
  • Vilkår for anvendelse
  • Rediger dine cookieindstillinger