My Smart UPS Modular Ultra shows "Battery not compatible"

Issue:

My Smart UPS Modular Ultra shows "Battery not compatible"


Product Line:

Smart UPS Modular Ultra


Environment:

All models, all serial numbers


Resolution:

There are three options for clearing this alarm:

  1. Upgrade the UPS to at least FW 17.0 for a permanent fix (Recommended)
  2. Wait four hours for the next compatibility check - the error usually clears the next time the system checks for compatibility
  3. Power cycle the battery using the thumbscrew on the front of the battery module - this will clear the error and restart communications

If the issue still persists, the battery will need to be replaced.

Schneider Electric Danmark

Se mere
Område:
Se mere
Område:

Brug for hjælp?

  • Produktvælger

    Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.

  • Få et tilbud

    Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.

  • Find forhandler

    Find den nærmeste Schneider Electric-distributør.

  • Hjælpecenter

    Find supportressourcer til alle dine behov på ét sted.

  • Produktdokumentation
  • Download af software
  • Produktvælger
  • Udskiftning og erstatning af produkter
  • Hjælp og kontaktcenter
  • Find forhandler
  • Få et tilbud
  • Find vores kontorer
  • Karriere
  • Virksomhedsprofil
  • Rapportér en forseelse
  • Tilgængelighed
  • Presserum
  • Investorer
  • EcoStruxure
  • Jobsøgning
  • Blog
  • Privatlivspolitik
  • Cookiemeddelelse
  • Vilkår for anvendelse
  • Rediger dine cookieindstillinger