EGU LRV = 4 mA Value
EGU URV = 20 mA Value
- Press the NEXT button twice and the word CONFIG will be displayed.
- Press ENTER and OUT DIR will be displayed
- Press NEXT 4 times and DISPEGU will be displayed
- Press ENTER and USE EGU will be displayed
- Press ENTER and EGU SEL will be displayed
- Press ENTER and the current engineering unit will be displayed
- Press NEXT until the desired engineering unit is displayed (i.e. FtH2O, inH2O, PSI...)
- When desired engineering unit is displayed, press ENTER and EGU LRV will be displayed
- Press ENTER and the cursor at the left side of the display will flash.
- Press ENTER and the left hand most digit will flash.
- Press NEXT until this digit matches the value of the most significant digit of the desired LRVvalue. Repeat procedure for the remaining 3 digits until the entire LRVvalue has been entered
- Press ENTER and SET DP will be displayed
- Press NEXT until the decimal point is in the correct location
- Press ENTER and EGU URV will be displayed.
- Press ENTER and flashing cursor will appear at the left side of display
- Press ENTER and the left most digit will flash
- Press NEXT until this digit matches the value of the most significant digit of the desired URVvalue. Repeat procedure for the remaining 3 digits until the entire URVvalue has been entered
- Press ENTER and SET DP will be displayed
- Press NEXT until the decimal point is in the correct location
- Press ENTER and CANCEL will be displayed
- Press NEXT and SAVE will be displayed
- Press ENTER and device will be returned to Measurement Display
- Complete
Udgivet til: Schneider Electric Danmark
Discontinued
Discontinued
Brug for hjælp?
Produktvælger
Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.
Få et tilbud
Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.
Find forhandler
Find den nærmeste Schneider Electric-distributør.
Hjælpecenter
Find supportressourcer til alle dine behov på ét sted.