Issue:
Saving the ATV320 Drives program with function blocks on the Multiloader programmer.
Product Line:
ATV320 with Multiloader device.
Environment:
All
Cause:
Getting an error message when trying to download the ATV320 program with function block using the multiloader.
Resolution:
When the ATV320 has ATVLogic running, you must stop the ATVLogic running before any multiloader transfer (you must set fbCd=STOP via keypad using ATV320 integrated Jog dial). Otherwise, the transfer will not be done.
Menus
-Config
-Full
-Function blocks
-FB command (fbCd)
set to Stop.
Now you can download the ATV320 program into the Multiloader.