Firmware Upgrade Procedure for Sage RTU
Issue:
How to upgrade firmware on Sage RTU devices securely and correctly.
Product:
Schneider Electric Sage RTU Series (SAGE 1X10, 1X30, 1X50, 2X00, 3030X)
Environment:
- Sage RTU running secure firmware
- Windows PC with Internet Explorer or Chrome
- Firmware update package (C3414-500-S02YZ_Firmware_Update.zip)
- Microsoft .NET Framework 3.5 or later
- Direct Ethernet or PPP connection
Cause:
Firmware upgrades are needed for security patches, feature enhancements, and compliance. Incorrect steps can cause configuration loss or RTU crash recovery mode.
Resolution:
Step 1. Preparation.
1.1- Backup current configuration via GUI (Up/Download tab → Get from RTU).
1.2.-Download firmware update zip (available Here) and extract tools: Config Converter and User Manager.
1.3.-Use Config Converter to update configuration to match new firmware revision.
1.4.-Use User Manager to create/update user package with roles and SSH keys.
Step 2. Upgrade Steps:
2.1.-Log in to RTU GUI with Up/Download privilege.
2.2.-Go to Up/Download tab.
2.3.- Upload files in order:
-
- Firmware: C3414-500-S02YZ_firmware.tar.gz
- Configuration: C3414-500-S02YZ_config.tar.gz
- User Info: Desc_Ver_Users.tar.gz
2.4.-Click Send to RTU.
2.5.- Perform Normal Reset and wait ~60 seconds.
2.6.- Verify firmware version under CPU Configuration.
Notes:
- The system will prompt for a reboot, as is required after uploading new configuration files.
- Enable SSH/HTTPS for secure mode.
- If RTU enters Crash Recovery mode, upload safe configuration via console.
Udgivet til: Schneider Electric Danmark
Brug for hjælp?
Produktvælger
Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.
Få et tilbud
Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.
Find forhandler
Find den nærmeste Schneider Electric-distributør.
Hjælpecenter
Find supportressourcer til alle dine behov på ét sted.