UI I2C communication alarm detected 1421 on Smart UPS Modular Ultra

Issue:

My Smart UPS Modular Ultra has UI I2C communication alarm detected 1421 on the display and/or NMC Web Interface


Product Line:

Smart UPS Modular Ultra


Environment:

All models, all serial numbers


Resolution:

If you see this alarm, please clear the alarm and perform a power cycle to the UPS.  You can follow this FAQ for a proper power cycle: https://www.se.com/us/en/faqs/FAQ000274118/.

Once you clear the alarm, please upgrade the UPS Firmware to 18.0 or greater.  If you are unable to clear the alarm with a power cycle, please proceed with the firmware upgrade, then clear the alarm.

Below are the FAQs on upgrading the UPS Firmware:

How to Install Smart-UPS Modular Ultra Firmware Using the Display and USB Port
Web Link - https://www.se.com/ie/en/faqs/FAQ000261838/

How do I update my Smart-UPS firmware using the web interface of my Network Management Card?
Web Link - https://www.se.com/ca/en/faqs/FA170679/

If the alarm stays after power cycling the UPS while on FW 18.0 or greater, please reach out to CCC Technical Support.

Schneider Electric Danmark

Se mere
Område:
Se mere
Område:
  • Produktdokumentation
  • Download af software
  • Produktvælger
  • Udskiftning og erstatning af produkter
  • Hjælp og kontaktcenter
  • Find forhandler
  • Projektrådgivning
  • Find vores kontorer
  • Schneider Electric Community
  • Karriere
  • Virksomhedsprofil
  • Rapportér en forseelse
  • Tilgængelighed
  • Presserum
  • Investorer
  • EcoStruxure
  • Jobsøgning
  • Blog
  • Privatlivspolitik
  • Cookiemeddelelse
  • Vilkår for anvendelse
  • Rediger dine cookieindstillinger