After upgrading to NetBotz 5.5 firmware, clips are no longer attached to e-mail alerts.

Issue:
After upgrading to NetBotz 5.5 firmware, clips are no longer attached to e-mail alerts.

Product Line:
NetBotz

Environment:
NBRK0750
NBWL0755
Botzware 5.5.0

Cause:
After upgrading to 5.5 some customers are experiencing an issue where e-mails are no longer sent.

Resolution:
This issue will be resolved in the 5.6 release but in the meantime, there is a workaround.

Go to the NetBotz top menu and choose Settings-->System-->E-mail
Regardless of "Connection Security" settings, make sure a user name is input into the "Authentications Settings" Username field.

User Name Field

This appears to resolve the issue based on the 5.5.0 upgrade.

Schneider Electric Danmark

Se mere
Område:
Se mere
Område:

Brug for hjælp?

Brug for hjælp?

Produktvælger

Produktvælger

Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.

Få et tilbud

Få et tilbud

Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.

Find forhandler

Find forhandler

Find den nærmeste Schneider Electric-distributør.

Hjælpecenter

Hjælpecenter

Find supportressourcer til alle dine behov på ét sted.

  • Produktdokumentation
  • Download af software
  • Produktvælger
  • Udskiftning og erstatning af produkter
  • Hjælp og kontaktcenter
  • Find forhandler
  • Projektrådgivning
  • Find vores kontorer
  • Schneider Electric Community
  • Karriere
  • Virksomhedsprofil
  • Rapportér en forseelse
  • Tilgængelighed
  • Presserum
  • Investorer
  • EcoStruxure
  • Jobsøgning
  • Blog
  • Privatlivspolitik
  • Cookiemeddelelse
  • Vilkår for anvendelse
  • Rediger dine cookieindstillinger