NetBotz 750/755/756: Firmware Update Precaution to Prevent Boot Failure
Issue:
Customers may encounter a “Trying to boot from SPI” message after a firmware update (particularly when updating from version 5.3.5 or later) or following a power interruption. This may result in the unit requiring a replacement.
Product Line:
NetBotz
SKUs affected:
- Netbotz 750/TAA/EU
- Netbotz 755/756/TAA/EU
Resolution:
Before starting any firmware update, please execute the following:
If the NetBotz is already on-line:
Verification before upgrade
This can be verified by logging in as root into the command line via console or SSH (shift X when asked to configure) and drop into the command line then type:
root@netbotz862729e5:~# fw_printenv check_rtc
The proper response is:
## Error: "check_rtc" not defined
The incorrect response is:
check_rtc=i2c read 0x68 9 1 0x8000; if itest.b *8000 > 20; then i2c mw 0x68 9 0x1F ; fi
To correct this:
1. Connect console cable to the appliance
2. Reboot the appliance
3. During the 5 second countdown press any key to enter to enter U-boot command line
4. Type fw_printenv check_rtc to verify if check_rtc exists.
If the output is, ## Error: "check_rtc" not defined, proceed with updating the firmware.
If the output is, check_rtc=i2c read 0x68 9 1 0x8000; if itest.b *8000 > 20; then i2c mw 0x68 9 0x1F ; fi
type the following commands to delete the check_rtc line:
· type: setenv check_rtc
· type: saveenv
· type: boot
5. Verify if check_rtc was cleared by executing step 4 and shows## Error: "check_rtc" not defined
6. Proceed with updating the firmware.
Note: Please ensure these steps are strictly followed to help prevent the unit from requiring an replacement.