{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
Search FAQs
This FAQ has been written for NEAL (North East Africa and Levant) region. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.
Why am I not able to establish communication with external batteries and my SURT15k/20K UPS?

Issue:

Cannot establish communications with external battery packs

Product Line:

Smart-UPS Online

Environment:

All SURT 15K and 20K models, All Serial Numbers

Cause:

Communications are sometimes slow to initialize when connecting external battery packs.

Resolution:
  • Disconnect all external battery packs - Wait at least 2 minutes
  • Connect first battery pack - Wait at least 2 minutes
  • Connect next battery pack - Wait at least 2 minutes
  • Continue until all battery packs are recognized and communicating with the UPS.

If issue persists, consult your users manual for additional troubleshooting methods.

Schneider Electric Egypt and North East Africa

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: