Can an I -Line breaker be converted to a Lug-in Lug-out breaker and vice versa? Can the I-Line shroud and connectors be replaced with lugs?

Issue:
Convert I-Line breaker to lugs on both ends breaker. Or lug-lug breaker be converted to an I-line breaker?  

Product Line:
I-Line Panelboards, Molded Case Circuit breakers

Environment:
I-Line Breakers VS Unit Mount Breakers

Cause:
Product modifications

Resolution:
The I-Line connector cannot be removed or retrofitted in the field or by the factory.  A new circuit breaker must be ordered with the lug in/out terminations.
A unit mount breaker, with lug in and lug out cannot be converted to an I-line breaker.
 