{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

What is a bPF fault on the ATS22 soft starter?

Issue:
bPF fault on the ATS22.

Product Line:
Altistart ATS22

Environment:
All

Cause:
Bypass contactor detected fault

Resolution:
Do a static test on the ATS22;
https://www.se.com/us/en/faqs/FA221890/
If test results indicate a shorted SCR or welded/stuck shorting contactor, replace the soft starter.
Reference the ATS22 installation guide (BBV51330)

Schneider Electric Hong Kong

Explore more
Explore more
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.