How to connect Unity Pro to a Modbus PLC through a TSXETG100 Ethernet gateway

Issue

How can Unity Pro connect to a Modbus PLC through a TSXETG100 Ethernet gateway?

Product Line

  • TSXETG100
  • Unity Pro

Environment

The TSXETG100 is used as the communication gateway between Unity Pro and the PLC.

Resolution

  1. Configure the PLC Modbus address in the TSXETG100

    • Open the TSXETG100 web interface by entering its IP address in a web browser.

ETG0100, connection

      • Log in to the TSXETG100.
      • Select Setup > Device List.

web page, ETG,

      • Add the Modbus address of the PLC to the device list.
      • Select Apply to save the configuration.
  1. Configure the PLC address in Unity Pro

    • Open the Unity Pro project.
    • Select PLC > Set Address.
    • unity Pro, Set address
    • In Media, select TCPIP.
    • In the Address field, enter the TSXETG100 IP address followed by a semicolon (;) and the PLC Modbus address.
    • connection configuration

    In this example:

    • 192.168.40.2 is the TSXETG100 IP address.
    • 1 is the Modbus address of the PLC.
  2. Connect to the PLC

    • Confirm the address configuration.
    • Select PLC > Connect.


Schneider Electric Hong Kong

Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact centre
  • Find our Offices
  • Get a Quote
  • Where to buy
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings