Is it possible to use PTC probe connected to encoder input on ATV340 (without encoder)?
It is possible. Encoder has to be configured to something, but usage of encoder has to be set to none. If it is set, encoder thermal monitoring can be activated and it will work.
Released for:Schneider Electric Hong Kong
Explore more
Range:
Altivar Machine ATV340
Articles that might be helpful
Show more articles
Discuss this topic with experts
Visit our Community for first-hand insights from experts and peers on this topic and more.