Unable to establish communication in PME with Eton93PM even when the webpage is accessible and the IP address pings OK.
Product Line
Power Monitorirng Expert third-party device type
Environment
PME communication with third-party devices
Cause
No communication to Eaton93PM in Power Monitoring Expert.
Resolution
- Log in to the Eaton93PM, select the Network option from the left side and select Reboot Now as shown on the screen shot below just below the "HTTP get test"
- It will take about 2 minutes for the reboot to compete, PME will see the device as soon as the reboot completes