How to switch between Local and Remote modes on the remote graphic HMI connected to an ATV212?

Issue:

Switch to local mode on ATV212 using the remote keypad.

 

Product Line:

ATV212, S-Flex

 

Environment:

All models with VW3A1101 connected

 

Cause:

Remote HMI does not have a LOC/REM button like the integral keypad.

 

Resolution:

The remote HMI, part# VW3A1101, has the F4 key assigned for LOC/REM switching. The active mode is indicated just above the F1 key.