Issue:
I got a "Slave Device Failure" Modbus exception when I read the Embedded Configuration Registers for a Smartlink device.
Resolution:
Embedded Configuration Registers for a Smartlink must by read with a block of 64 Registers
Example:
I got a "Slave Device Failure" Modbus exception when I read the Embedded Configuration Registers for a Smartlink device.
Resolution:
Embedded Configuration Registers for a Smartlink must by read with a block of 64 Registers
Example:
- for Channel_1 - Input 1 => you need to poll 64 registers from Register 20010
- for Channel_1 - Input 2 => you need to poll 64 registers from Register 20074
- for Channel_7 - Input 2 => you need to poll 64 registers from Register 20778
Released for: Schneider Electric Hong Kong






Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.