In EcoStruxure Machine SCADA Expert, the function DBExecute can be used to write some data in SQL Database.
There is a limitation with this function. The maximum length of an SQL statement 1024 characters.
The goal of this article is to explain how to send more than 1024 characters in the SQL Databse, with the function DBExecute
This article is applicable for EcoStruxure Machine SCADA Expert, all version
To execute SQL commands longer than 1024 characters with DBExecute() or DBCursorOpenSQL(), need to break the SQL statement into fragments, storing those fragments in string tags, and then using tag pointers to reference those tags.
For example:
There is a limitation with this function. The maximum length of an SQL statement 1024 characters.
The goal of this article is to explain how to send more than 1024 characters in the SQL Databse, with the function DBExecute
This article is applicable for EcoStruxure Machine SCADA Expert, all version
To execute SQL commands longer than 1024 characters with DBExecute() or DBCursorOpenSQL(), need to break the SQL statement into fragments, storing those fragments in string tags, and then using tag pointers to reference those tags.
For example:
$SQL1 = "first 1000 chars"
$SQL2 = "second 1000 chars"
$DBExecute("ConnName", "{SQL1}{SQL2}")
$SQL2 = "second 1000 chars"
$DBExecute("ConnName", "{SQL1}{SQL2}")
Released for: Schneider Electric Hong Kong


Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.