Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
Can Auxiliary Contact Blocks Be Mounted When Using GV2GH7 Line Spacer?
Issue:
Using the GVAE auxiliary contact blocks when GV2GH7 line spacer is used on GV2P Motor Circuit Breakers

Product Line:
GV2P, GV2

Environment:
Contactors and Starters

Resolution:
Front mounted auxiliary contact blocks (GVAE**) when a GV2GH7 line spacer cannot be mounted. Recommended to use the Left Hand Side Mounted auxiliary contact blocks (GVAN**) instead.

Schneider Electric Hong Kong

Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range:

Need help?

  • Product Selector

    Quickly and easily find the right products and accessories for your applications.

  • Get a Quote

    Start your sales enquiry online and an expert will connect with you.

  • Where to buy?

    Easily find the nearest Schneider Electric distributor in your location.

  • Help Centre

    Find support resources for all your needs, in one place.

  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact centre
  • Find our Offices
  • Get a Quote
  • Where to buy
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings