Illustration example, "autorun" option for BMEP582020
This problem only occurs when a configuration modification (addition/deletion of a module, a rack, etc.) is made and followed by an online build.
The only solution in this case is to do a "rebuild all" and transfer the application to the PLC.
This operating issue is corrected in version 16 of Control Expert.