Issue
The following error is shown when an ION meter is opened in ION Setup using single device mode:
"Potential Security Risk. Certificate Error Summary. Detected an invalid security certificate in use. Certificate has expired. The certificate is not trusted because it is self-signed. Error code: RemoteCertificateNameMismatch, RemoteCertificateChainErrors. The security certificate is not trusted by your computer's operating system. This may be caused by a misconfiguration or an attacker intercepting your connection. Only press Proceed if you are sure the connection is secure."
Product Line
ION Meters
Environment
ION Setup
Cause
This message is caused when a meter is configured to use Secure ION, or ION over TLS. By default, devices that support Secure ION include a self-signed SSL certificate. If using ION Setup single device mode, you must accept the certificate every time you connect to the device using ION Setup.
Resolution
To increase security and prevent this message from re-appearing in single device mode, use a Certificate Authority (CA). This can be provided by IT.
For more information on secure ION, see the PM8000 online guide https://product-help.schneider-electric.com/PowerLogic-PM8000/en-us/content/03-communications/secure-ion.htm?tocpath=Communications|ION|Secure ION|_____0
Released for: Schneider Electric Hong Kong
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.