Issue
During troubleshooting, there may be a need to power cycle a Link150 gateway remotely. Power cycling the gateway releases existing connections which can allow other software to communicate to the 7801 port for example, which only allows 1 connection at a time.
Product Line
Link150/EGX150
Environment
Link150 Web Server
Resolution
*Warning: Installation and maintenance of this device should only be performed by qualified, competent personnel that have appropriate training and experience with high voltage and current devices. Failure to follow the instructions / warnings in the Meter Installation Guide can result in permanent damage to the meter, severe injury or death.
1. Log into the Link150 web page. Refer to https://www.se.com/us/en/faqs/FA299649/ for the default login information.
2. Navigate to the Settings tab > Communication > IP Network Services:
3. Check or uncheck the box to enable ION Pass Through, then click Apply Changes. The Link150 will reboot.
4. Refresh the page and log back into the Link150 web server.
5. Repeat the above steps to set the ION Pass Through back to its previous setting, which will reboot the Link150 again.
Released for: Schneider Electric Hong Kong
Issue
During troubleshooting, there may be a need to power cycle a Link150 gateway remotely. Power cycling the gateway releases existing connections which can allow other software to communicate to the 7801 port for example, which only allows 1 connection at a time.
Product Line
Link150/EGX150
Environment
Link150 Web Server
Resolution
*Warning: Installation and maintenance of this device should only be performed by qualified, competent personnel that have appropriate training and experience with high voltage and current devices. Failure to follow the instructions / warnings in the Meter Installation Guide can result in permanent damage to the meter, severe injury or death.
1. Log into the Link150 web page. Refer to https://www.se.com/us/en/faqs/FA299649/ for the default login information.
2. Navigate to the Settings tab > Communication > IP Network Services:
3. Check or uncheck the box to enable ION Pass Through, then click Apply Changes. The Link150 will reboot.
4. Refresh the page and log back into the Link150 web server.
5. Repeat the above steps to set the ION Pass Through back to its previous setting, which will reboot the Link150 again.
Released for: Schneider Electric Hong Kong
Need help?
Start here!
Find answers now. Search for a solution on your own, or connect with one of our experts.
Contact Support
Reach out to our customer care team to receive more information, technical support, assistance with complaints and more.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Search FAQs
Search topic-related frequently asked questions to find answers you need.
Contact Sales
Start your sales enquiry online and an expert will connect with you.