If the Schneider Electric CT's are used the following table and diagram show how the power cables should be placed.
Motor In | Primary (A) | Secondary (A) | No. of Pass(es) | Reference |
3.5 to 10.5 | 30 | 1 | 3 | LUTC0301 |
5.2 to 16 | 30 | 1 | 2 | LUTC0301 |
10.5 to 32 | 30 | 1 | 1 | LUTC0301 |
17.5 to 53 | 50 | 1 | 1 | LUCT0501 |
35 to 105 | 100 | 1 | 1 | LUCT1001 |
70 to 210 | 200 | 1 | 1 | LUTC2001 |
140 to 420 | 400 | 1 | 1 | LUTC4001 |
280 to 840 | 800 | 1 | 1 | LUTC8001 |