{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
Search FAQs
What is the maximum length of the input loop of the Preventa XPSAF5130 module?

The Preventa XPSAF5130 module is designed, amongst other things, to monitor emergency stops via its two input loops S11 - S12 and S21 - S22.

In industrial applications, emergency stops may be located some distance away from the factory and the safety module which monitors them mustn't cost too much.

For a possible solution to the cost issue, several emergency stops can be wired in series on the same loop; this is permitted by the safety regulations but not for all the other safety devices such as sensors, etc.

The line resistance of both loops on the Preventa XPSAF5130 module must be less than 90 ohms.

To calculate the maximum length of the emergency stop monitoring loop, you need to know the linear resistance of the cable.

Calculation example

For a cable with maximum linear resistance of the bare copper core at 20°C of 13.3 ohms/km, the maximum length of the loop will be:
90 ohms/13.3 = 6.7 km

It is also necessary to consider the contact resistance of the emergency stop contact blocks.

The emergency stops could therefore be distributed over a distance of 5 to 6 km.

NOTE: XPSAF* has been replaced by XPSUAF* range of safety relays. This FAQ is for information purposes only.

Schneider Electric Ireland

Explore more
Product:
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Product:
Range: