{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

M241 control Lexium 23A via CANopen, LXM23 sometimes can not be powered via MC_Power_LXM23 without any error.

Its generally in every application needed to read out the actual drive state (CIA Get State) for "OPERATIONAL" at first, before any function block will be called !
The CIA Get State function block has to be called cyclic and the Enable input must be toggled! Please see attached demo program.

This is needed especially when the drives will be switched on after the PLC has booted otherwise the PLC goes into Nodeguard error, and the MC_Power for Lexium 23
remains in state 991.

Schneider Electric Ireland

Attachment(s)

Get_state.jpgGet_state.jpg [69.68 KB]
Explore more
Range:
Lexium 28 & Motors
Explore more
Range:
Lexium 28 & Motors
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.