Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
How to set up a fault reset function on ATV630 Process drive?

Article available in these languages: Japanese

Issue:
Fault reset function on the ATV630

Product Line:
Altivar ATV630

Environment:
All Process drives

Cause:
Fault reset function needed

Resolution:
Go into Menu 5 complete settings and enter
Go down to submenu 5.11 Error/Warning Handing and enter
Go to Fault Reset and Enter.
Go to Fault Reset Assignment
Choose digital input desired to act as a fault reset.

Schneider Electric Ireland

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Centre
  • Find our Offices
  • Where to buy
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings