How do you fit an outgoer larger than 63A in a Acti9 distribution board?

It is possible to have up to 100A outgoer in distribution boards by fitting a 100A terminal block SEA9TB1001 (1 per pole) to the pan and then cable out into a iC120H in a din rail enclosure.

Note: the maximum is 100A.