How can we help you today?

Can a standalone RCD be fitted onto the outgoing way of an Isobar and Acti9 Distribution Board?

The Isobar Distribution Boards outgoing ways are designed to be fitted only with iC60H MCB's up to and including 63A and RCBO's up to 45A.
RCD's and other din rail devices cannot be fitted.

They should be fitted on a din rail.
- In case of single phase boards, a multiservice single phase distribution board has a din rail already fitted.
- For a three phase board an extension box with a din rail of 17 single pole ways width is available.

Part number SEA9BNEX034N can be used for Acti9 Isobar distribution boards.