What causes BLF fault on ATV340 and how do I correct it?

Issue:
BLF [Brake Control Fault] on an ATV340 series drive.

Product Line:
Altivar 340 Drive

Environment:
Brake Logic Control function is being used.

Cause:
- Brake release current not reached.
- Brake engages frequency threshold [Brake engage freq] bEn only regulated when brake logic control is assigned.

Resolution:
  1. Verify the drive/motor connection.
  2. Verify the motor windings.
  3. Verify the [Brk Release Current] Ibr and [Brake release I Rev] Ird settings.
  4. Apply the recommended settings for [Brake engage freq] bEn.