How do you configure the ATV312 drive for CANopen control?
Issue:
ATV312 configuration for CANopen control
Product line:
Altivar ATV31 and ATV312
Environment:
All models, all serial numbers
Cause:
Programming the ATV312 drive for CANopen control.
Resolution:
Programming
Communications MENU (COM)
AdCO= Canopen address
bdCO= CANopen bit rate
ErCO= Error Code optional
Control menu (CTL)
LAC= L3
Fr1=Network
rFC= Fr1
CHCF= SEP
CD1= network
CCS=CD1
Reference Programming manual BBV46385
ATV312 configuration for CANopen control
Product line:
Altivar ATV31 and ATV312
Environment:
All models, all serial numbers
Cause:
Programming the ATV312 drive for CANopen control.
Resolution:
Programming
Communications MENU (COM)
AdCO= Canopen address
bdCO= CANopen bit rate
ErCO= Error Code optional
Control menu (CTL)
LAC= L3
Fr1=Network
rFC= Fr1
CHCF= SEP
CD1= network
CCS=CD1
Reference Programming manual BBV46385