ION Enterprise web based report prompts to enter a user name and password to access the data source.

Issue
When attempting to generate a web based report there is a prompt for entering a user name and password to access the data source:

Web Reporter User Name and Password Prompt

Product Line
ION Enterprise 6.x

Environment
Reporting

Cause
Login credentials are changed or may not be specified so that WebReporter (Reporting Services) can access the IONReportDataSource.

Resolution
Follow the procedure below to set the correct login credentials.
1.Open the web browser and open the http://<server name>/Reports or http://<server name>/Reports$ION virtual root.
2. Open the IONReportDataSource.
3. Under the Connect Using, select the radio button "Credentials stored securely in the report server".
4. Enter the following user information:
User Name: IONUser
​Password: IONisgreat!
5. Click on Apply to apply the changes.

User Name and Password Steps

שניידר אלקטריק ישראל

גלה עוד
טווח:
גלה עוד
טווח:

זקוק לעזרה?

  • בורר מוצרים

    חפשו ברשת של מפיצים מאומתים עם יותר מ-15,000 שקעי למכירה ברחבי העולם.

  • קבלת הצעת מחיר

    התחילו את בקשת הקניה בצורה מקוונת ונציג מכירות ייצור עמכם קשר.

  • היכן לקנות?

    אתר בקלות את מפיץ Schneider Electric הקרוב ביותר אליך.

  • מרכז העזרה

    חפשו משאבי תמיכה לכל הצרכים שלכם במקום אחד.

  • תיעוד מוצרים
  • בורר המוצר
  • מוצרים חלופיים והחלפה
  • מרכז עזרה ויצירת קשר
  • איתור סניפי שניידר אלקטריק
  • היכן לקנות
  • משרות
  • פרופיל חברה
  • דיווח על התנהגות בלתי הולמת
  • נגישות
  • חדר חדשות
  • משקיעים
  • EcoStruxure
  • חיפוש משימה
  • בלוג
  • מדיניות שמירה על פרטיות
  • הודעה על קובצי Cookie
  • תנאי שימוש
  • Change your cookie settings