Why is the Time Sync Count not increasing?

In each ION Meter, the Diagnostic module has a "Time Sync Count" output register. This register indicates how many time-synchronization signals have been received. The value increases with each signal received. In some cases, this register is not increasing, although it is obvious the meter has been re-synchronized.

This is most likely because the synchronization type is set to NTP (Network Time Protocol). Using the ION synchronization, ION Enterprise detects that the meter if off-sync, and will send a sync signal.
When using NTP, the meter ignores the sync signals coming from ION Enterprise. With this setting, the meter doesn't actually RECEIVE a synchronization signal, as it will synchronize by itself on a network clock. That's why the time sync counter doesn't increase when NTP is selected.

שניידר אלקטריק ישראל

גלה עוד
טווח:
גלה עוד
טווח:

זקוק לעזרה?

  • בורר מוצרים

    חפשו ברשת מפיצים מאומתים עם יותר מ-15,000 נקודות מכירה ברחבי העולם.

  • קבלת הצעת מחיר

    התחילו את בקשת הקניה בצורה מקוונת ונציג מכירות ייצור עמכם קשר.

  • היכן לקנות?

    אתר בקלות את מפיץ Schneider Electric הקרוב ביותר אליך.

  • מרכז העזרה

    חפשו משאבי תמיכה לכל הצרכים שלכם במקום אחד.

  • תיעוד מוצרים
  • בורר המוצר
  • מוצרים חלופיים והחלפה
  • מרכז עזרה ויצירת קשר
  • איתור סניפי שניידר אלקטריק
  • היכן לקנות
  • הקהילה של Schneider Electric
  • משרות
  • פרופיל חברה
  • דיווח על התנהגות בלתי הולמת
  • נגישות
  • חדר חדשות
  • משקיעים
  • EcoStruxure
  • חיפוש משימה
  • בלוג
  • מדיניות שמירה על פרטיות
  • הודעה על קובצי Cookie
  • תנאי שימוש
  • Change your cookie settings