How do you set up the ATV61/71 for Profibus communications?

Issue:
ATV61/71 set up for Profibus communications.


Product Line:
Altivar ATV61 and ATV71


Environment:
All


Cause:
Profibus network setup configuration.


Resolution:
Refer to the atv71_profibus _EN_V1 manual

Addressing is set up via the 8 dip switch settings on the option card.
Connector Pinouts:  Sub D 9 pin female connector.
Pin 1
Pin 2
Pin 3 RX/TX data (-)
Pin 4
Pin 5 DGND Ground
Pin 6 5vdc
Pin 7
Pin 8 RX/TX data (+)
Pin 9

This Card does support 8 series Mode:  The switch furthest to the left sets the ATV71/61 drive in 8 Series mode
Last switch on the left set to 1=  makes the drive 8 series compatibility mode
Last switch on the left set to 0=  makes the drive ATV61/71 mode.

Setting up the drive for controlling the drive via the Profibus command and speed reference signals.
Menu 1.6 Command
Ref 1 channel set to Com card
Profile set to IO
CMD switching set to Channel 1 active
CMD channel 1 set to Com card


שניידר אלקטריק ישראל

גלה עוד
טווח:
גלה עוד
טווח:

זקוק לעזרה?

זקוק לעזרה?

בורר מוצרים

בורר מוצרים

חפשו ברשת מפיצים מאומתים עם יותר מ-15,000 נקודות מכירה ברחבי העולם.

קבלת הצעת מחיר

קבלת הצעת מחיר

התחילו את בקשת הקניה בצורה מקוונת ונציג מכירות ייצור עמכם קשר.

היכן לקנות?

היכן לקנות?

אתר בקלות את מפיץ Schneider Electric הקרוב ביותר אליך.

מרכז העזרה

מרכז העזרה

חפשו משאבי תמיכה לכל הצרכים שלכם במקום אחד.

  • תיעוד מוצרים
  • בורר המוצר
  • מוצרים חלופיים והחלפה
  • מרכז עזרה ויצירת קשר
  • איתור סניפי שניידר אלקטריק
  • היכן לקנות
  • הקהילה של Schneider Electric
  • משרות
  • פרופיל חברה
  • דיווח על התנהגות בלתי הולמת
  • נגישות
  • חדר חדשות
  • משקיעים
  • EcoStruxure
  • חיפוש משימה
  • בלוג
  • מדיניות שמירה על פרטיות
  • הודעה על קובצי Cookie
  • תנאי שימוש
  • Change your cookie settings