Video: How can you turn off the flashing red caution LED on the ATV630 and ATV930 process drives?
Issue:
Turning off the flashing red caution LED on the ATV630 and ATV930 process drives.
Product Line:
Altivar ATV630 and ATV930
Environment:
All
Cause:
There is a default alarm set in the warnings group for Analog input AI1, AI2, and AI3 that has to be turned off.
Resolution:
The warning LED is triggered when a Warning Group item is activated. The factory default has many items selected for monitoring under Warning Group 1. A typical warning is caused when an analog input is configured for 4-20mA, but the signal is not present.
From the Main menu:
See attachment
Now the red flashing warning light will turn off.
Turning off the flashing red caution LED on the ATV630 and ATV930 process drives.
Product Line:
Altivar ATV630 and ATV930
Environment:
All
Cause:
There is a default alarm set in the warnings group for Analog input AI1, AI2, and AI3 that has to be turned off.
Resolution:
The warning LED is triggered when a Warning Group item is activated. The factory default has many items selected for monitoring under Warning Group 1. A typical warning is caused when an analog input is configured for 4-20mA, but the signal is not present.
From the Main menu:
- Scroll to Complete Settings and press OK
- Select Error Warning Handling and press OK
- Select Warnings Group Configuration and press OK
- Select Warn group 1 definition and press OK
- Now (almost halfway down the list) uncheck "AI1 4-20 Warning", "AI2 4-20 Warning", and "AI3 4- 20 Warning" boxes.
See attachment
Now the red flashing warning light will turn off.
פורסם עבור: שניידר אלקטריק ישראל




זקוק לעזרה?
בורר מוצרים
חפשו ברשת מפיצים מאומתים עם יותר מ-15,000 נקודות מכירה ברחבי העולם.
קבלת הצעת מחיר
התחילו את בקשת הקניה בצורה מקוונת ונציג מכירות ייצור עמכם קשר.
היכן לקנות?
אתר בקלות את מפיץ Schneider Electric הקרוב ביותר אליך.
מרכז העזרה
חפשו משאבי תמיכה לכל הצרכים שלכם במקום אחד.