How do I perform ATV630 and ATV930 Basic Programming?

Issue:
Basic Programming on an Altivar Process Drive.

Product Line:
Altivar Process Drive (ATV630, ATV930, ATV650, ATV950, ATV660, ATV960, ATV680, ATV980)

Environment:
All serial numbers for Altivar Process Drive

Cause:
Initial setup / maintenance

Resolution:
Using the keypad or our SoMove programming software, be sure to go through the Simply Start Menu to perform your basic settings:

From the Main Menu select [Simply start]:

[Motor Standard] bFr -            50Hz IEC or 60Hz NEMA- motor nameplate

[Nominal motor power] nPr -   Motor HP - motor nameplate

[Nom Motor Voltage] UnS -      Motor voltage - motor nameplate

[Nom Motor Current] nCr -       Motor FLA - motor nameplate

[Nominal Motor Freq] FrS -      60Hz in the US - motor nameplate

[Nominal Motor Speed] nSP - Actual motor max speed, not Synchronous speed unless it is a synchronous motor - motor nameplate

[2/3-Wire Control] tCC -           Factory default is '2-Wire Control'

[Max Frequency] tFr -              Max frequency of the motor, usually 60Hz - motor nameplate

[Autotuning] tUn -                    No Action, Apply Autotuning, Erase Autotuning

[Autotuning Status] tUS -         Displays 'Not Done' unless Autotuning is performed

[Motor Th Current] ItH -            Motor thermal current - motor nameplate - used to set the motor overload protection level

[Acceleration] ACC -                 Acceleration time in seconds

[Deceleration] dEC -                 Deceleration time in seconds

[Low Speed] LSP -                    Minimum speed, drive will never run lower than this speed when given a run command

[High Speed] HSP -                  Maximum speed, drive will never run higher than this speed when given a run command


In many instances these parameters will be enough to sufficiently program a drive. If any further programming is required (such as PID, command/reference switching, hoisting, etc), please refer to the applicable Programming Manual for your drive.

Refer to the applicable manual for further details:
ATV600 series Programming Manual
ATV900 series Programming Manual

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

שניידר אלקטריק ישראל

גלה עוד
טווח:
גלה עוד
טווח:

זקוק לעזרה?

זקוק לעזרה?

בורר מוצרים

בורר מוצרים

חפשו ברשת מפיצים מאומתים עם יותר מ-15,000 נקודות מכירה ברחבי העולם.

קבלת הצעת מחיר

קבלת הצעת מחיר

התחילו את בקשת הקניה בצורה מקוונת ונציג מכירות ייצור עמכם קשר.

היכן לקנות?

היכן לקנות?

אתר בקלות את מפיץ Schneider Electric הקרוב ביותר אליך.

מרכז העזרה

מרכז העזרה

חפשו משאבי תמיכה לכל הצרכים שלכם במקום אחד.

  • תיעוד מוצרים
  • בורר המוצר
  • מוצרים חלופיים והחלפה
  • מרכז עזרה ויצירת קשר
  • איתור סניפי שניידר אלקטריק
  • היכן לקנות
  • הקהילה של Schneider Electric
  • משרות
  • פרופיל חברה
  • דיווח על התנהגות בלתי הולמת
  • נגישות
  • חדר חדשות
  • משקיעים
  • EcoStruxure
  • חיפוש משימה
  • בלוג
  • מדיניות שמירה על פרטיות
  • הודעה על קובצי Cookie
  • תנאי שימוש
  • Change your cookie settings