How to reset the Digital Input count on a CM2000

Issue
Customer would like to reset the digital input status counter on the CM2000.

Product Line
CM2000 series

Environment
Modbus Register writes

Cause
The CM2000 does not have a digital input status counter reset command.

Resolution
Using Modbus Tester, write a value of zero (0) to the desired registers. Below is an excerpt of the CM2000 Modbus Register list that details the Digital Input's registers.

RegistersRange
Input 1 Count2404 - 24050 to 99,999,999
Input 2 Count2409 - 24100 to 99,999,999
Input 3 Count2414 - 24150 to 99,999,999
Input 4 Count2419 - 24200 to 99,999,999
Input 5 Count2424 - 24250 to 99,999,999
Input 6 Count2429 - 24300 to 99,999,999
Input 7 Count2434 - 24350 to 99,999,999
Input 8 Count2439 - 24400 to 99,999,999


In the following example, a CM2350's Input 1 Count is going to be reset. The necessary parameters are as follows:

  • Gateway IP Address: 10.167.244.21
  • CM2350 Device ID: 9
  • Starting Register: 2404

Once all the parameters have been specified, press Write to reset the value.

IMG1

שניידר אלקטריק ישראל

גלה עוד
מוצר:
גלה עוד
מוצר:

זקוק לעזרה?

זקוק לעזרה?

בורר מוצרים

בורר מוצרים

חפשו ברשת מפיצים מאומתים עם יותר מ-15,000 נקודות מכירה ברחבי העולם.

קבלת הצעת מחיר

קבלת הצעת מחיר

התחילו את בקשת הקניה בצורה מקוונת ונציג מכירות ייצור עמכם קשר.

היכן לקנות?

היכן לקנות?

אתר בקלות את מפיץ Schneider Electric הקרוב ביותר אליך.

מרכז העזרה

מרכז העזרה

חפשו משאבי תמיכה לכל הצרכים שלכם במקום אחד.

  • תיעוד מוצרים
  • בורר המוצר
  • מוצרים חלופיים והחלפה
  • מרכז עזרה ויצירת קשר
  • איתור סניפי שניידר אלקטריק
  • היכן לקנות
  • הקהילה של Schneider Electric
  • משרות
  • פרופיל חברה
  • דיווח על התנהגות בלתי הולמת
  • נגישות
  • חדר חדשות
  • משקיעים
  • EcoStruxure
  • חיפוש משימה
  • בלוג
  • מדיניות שמירה על פרטיות
  • הודעה על קובצי Cookie
  • תנאי שימוש
  • Change your cookie settings