איך נוכל לעזור לך היום?

Connecting an EGX150 to a serial RS485

Issue
The Serial port for the EGX150 uses an RJ45 connector, which is different from the standard RS-485 connector.

Product Line
Link150, EGX150

Environment
EGX150 serial connections

Cause
The EGX150 does not use the standard RS-485 connector.

Resolution

Table 1: Connector RJ 45 Pinout

Pin Number

Color

Signal name

Description

1

Orange/White striped

Rx-

Receive Data -

2

Orange

Rx+

Receive Data +

3

NC

No Connection

4

Blue

Tx+

Transmit Data +

5

Blue/white striped

Tx-

Transmit Data -

6

-

NC

No Connection

7

-

NC

No connection

8

-

GND

Ground












Connect, using a straight through RJ45 cable to the RS-485 port on your EGX150.
Cut the other end (that is to be connected to your slave device) to expose the wires.

A1. 2-Wire RS-485 connection


Use the Blue wire as the positive (+) and the Blue/White striped wire as the negative (-)

A1. 2-Wire RS-485 connection

A2. RS-485 2-Wire with Link150 Cable Adapter Connection Diagram

A2. RS-485 2-Wire with Link150 Cable Adapter Connection Diagram


B1. 4-Wire RS-485 connection

B1. 4-Wire RS-485 connection

Table 2: RJ45 Master/Slave Pinout

RJ45 Pin Number

Master

Slave

1

Rx-

Tx-

2

Rx+

Tx+

4

Tx+

Rx+

5

Tx-

Rx-









B2. RS-485 4-Wire with Link150 Cable Adapter Connection Diagram


B2. RS-485 4-Wire with Link150 Cable Adapter Connection Diagram


Kindly refer to the EGX150 User Guide for details on how to wire the RS-485 port.

שניידר אלקטריק ישראל

גלה עוד
טווח:
גלה עוד
טווח:
  • תיעוד מוצרים
  • בורר המוצר
  • מוצרים חלופיים והחלפה
  • מרכז עזרה ויצירת קשר
  • איתור סניפי שניידר אלקטריק
  • היכן לקנות
  • הקהילה של Schneider Electric
  • משרות
  • פרופיל חברה
  • דיווח על התנהגות בלתי הולמת
  • נגישות
  • חדר חדשות
  • משקיעים
  • EcoStruxure
  • חיפוש משימה
  • בלוג
  • מדיניות שמירה על פרטיות
  • הודעה על קובצי Cookie
  • תנאי שימוש
  • Change your cookie settings