Can an ATV680 Active Front End drive run with unbalanced input voltage?

Issue:
ATV680 running with unbalanced input voltage

Product Line:
Altivar 680 Process Drives

Environment:
All

Cause:
Site line voltage is unbalanced

Resolution:
It is NOT recommended to operate an ATV680 AFE on a 480V power system with a voltage unbalance of 4% to 7.5%. This is far outside the specification of the drive.
The mains voltage must comply with the requirements according to IEC 60038 and EN 50160:
- Unbalance between phases: < 2 %
- Total harmonic factor THD(v): < 10 %
- Maximum single harmonic: < 5 %
With this supply voltage the drive complies with the specified THDi value.

If the voltage unbalance is 2 … 4% the drive will work but the THDi value will be higher than specified. A voltage unbalance of more than 4% will harm the drive. The input IGBT might overheat and/or the fuses might blow due to unsymmetrical input current. There is also a risk of oscillations if the voltage controller is not able to keep DC bus voltage constant.

שניידר אלקטריק ישראל

גלה עוד
טווח:
סיווג:
גלה עוד
טווח:
סיווג:

זקוק לעזרה?

זקוק לעזרה?

בורר מוצרים

בורר מוצרים

חפשו ברשת מפיצים מאומתים עם יותר מ-15,000 נקודות מכירה ברחבי העולם.

קבלת הצעת מחיר

קבלת הצעת מחיר

התחילו את בקשת הקניה בצורה מקוונת ונציג מכירות ייצור עמכם קשר.

היכן לקנות?

היכן לקנות?

אתר בקלות את מפיץ Schneider Electric הקרוב ביותר אליך.

מרכז העזרה

מרכז העזרה

חפשו משאבי תמיכה לכל הצרכים שלכם במקום אחד.

  • תיעוד מוצרים
  • בורר המוצר
  • מוצרים חלופיים והחלפה
  • מרכז עזרה ויצירת קשר
  • איתור סניפי שניידר אלקטריק
  • היכן לקנות
  • הקהילה של Schneider Electric
  • משרות
  • פרופיל חברה
  • דיווח על התנהגות בלתי הולמת
  • נגישות
  • חדר חדשות
  • משקיעים
  • EcoStruxure
  • חיפוש משימה
  • בלוג
  • מדיניות שמירה על פרטיות
  • הודעה על קובצי Cookie
  • תנאי שימוש
  • Change your cookie settings