Advantys DTM – Bad DDDT structure from Advantys with custom Labels in Unity Pro V13.

Goals and Symptoms

Operating with Unity Pro V13 with an application using TeSys and STB devices, after import of custom labels in Advantys, the DDDT structure is not correct.

Facts and changes

It is observed that Advantys is exporting the variables in different order than expected.
This wrong behaviour is related to Advantys DTM.

Causes and Fixes

As workaround follow the steps below with a ‘’fake’’ modification and build to recover normal situation.
Launch Advantys configuration software from the DTM browser and do a small modification by opening the module editor of any module in the Advantys island. Build the advantys configuration .

Revert the change you have done and rebuild the island again. Then the variables are properly aligned in Unity Pro.

שניידר אלקטריק ישראל

גלה עוד
טווח:
גלה עוד
טווח:

זקוק לעזרה?

זקוק לעזרה?

בורר מוצרים

בורר מוצרים

חפשו ברשת מפיצים מאומתים עם יותר מ-15,000 נקודות מכירה ברחבי העולם.

קבלת הצעת מחיר

קבלת הצעת מחיר

התחילו את בקשת הקניה בצורה מקוונת ונציג מכירות ייצור עמכם קשר.

היכן לקנות?

היכן לקנות?

אתר בקלות את מפיץ Schneider Electric הקרוב ביותר אליך.

מרכז העזרה

מרכז העזרה

חפשו משאבי תמיכה לכל הצרכים שלכם במקום אחד.

  • תיעוד מוצרים
  • בורר המוצר
  • מוצרים חלופיים והחלפה
  • מרכז עזרה ויצירת קשר
  • איתור סניפי שניידר אלקטריק
  • היכן לקנות
  • הקהילה של Schneider Electric
  • משרות
  • פרופיל חברה
  • דיווח על התנהגות בלתי הולמת
  • נגישות
  • חדר חדשות
  • משקיעים
  • EcoStruxure
  • חיפוש משימה
  • בלוג
  • מדיניות שמירה על פרטיות
  • הודעה על קובצי Cookie
  • תנאי שימוש
  • Change your cookie settings