What can cause an EPFI [External Error] fault on an ATV340 and how do I correct it?
Issue:
Customer is experiencing an EPFI fault on their ATV340 series drive.
Product line:
ATV340
Environment:
All
Cause:
Resolution:
Review the External Error assignment in the Error/Warning handling menu. If EtF [Ext Error Assign} is set to anything other than No:not assigned (default), investigate the assigned input or bit to see what is triggering the External Error.
If EtF is set to No, the EPF1 is triggered due to a communication issue.
Possible causes include:
https://www.se.com/ww/en/download/document/NVE61653/
Customer is experiencing an EPFI fault on their ATV340 series drive.
Product line:
ATV340
Environment:
All
Cause:
Event triggered by an wired to a digital input or triggered by a bit via communication network.
An external error has been triggered via Embedded Ethernet.
Resolution:
Review the External Error assignment in the Error/Warning handling menu. If EtF [Ext Error Assign} is set to anything other than No:not assigned (default), investigate the assigned input or bit to see what is triggering the External Error.
If EtF is set to No, the EPF1 is triggered due to a communication issue.
Possible causes include:
- duplicate IP address on the network
- improper IP address/subnet mask/gateway settings
- FDR (Fast Device Replacement) error
- Incorrect Drive configuration when using ODVA assemblies 20/70 or 21/71
https://www.se.com/ww/en/download/document/NVE61653/
פורסם עבור: שניידר אלקטריק ישראל


זקוק לעזרה?
בורר מוצרים
חפשו ברשת מפיצים מאומתים עם יותר מ-15,000 נקודות מכירה ברחבי העולם.
קבלת הצעת מחיר
התחילו את בקשת הקניה בצורה מקוונת ונציג מכירות ייצור עמכם קשר.
היכן לקנות?
אתר בקלות את מפיץ Schneider Electric הקרוב ביותר אליך.
מרכז העזרה
חפשו משאבי תמיכה לכל הצרכים שלכם במקום אחד.