Is it possible to connect non-referenced pulse energy meter in Smartlink ELEC ? How to configure the demand power?

It is highly recommended to use referred references in Schneider Electric catalogue.
If use non-referenced pulse energy meter, you need to make herebelow configuration.
Power = Energy/Time = (3600 x Weight of each pulse)/time is seconds between the 2 last pulses
This gives an average power calculated in the recent past, as it is calculated between the 2 last pulses received by the Smartlink EL B from the connected meter. The minimum width of pulse must be 50ms.
i.e., if 4 seconds between 2 last pulses, and weight is 10 Wh per pulse (in that example the unit is Wh), calculation will give 3600*10/4 = 9000 W
It is set to zero if no new pulse has been received after 3 times the time between the 2 last pulses.
Precision is 5% when frequency of pulses is less or equal to 5 Hz (5 pulses per second)

שניידר אלקטריק ישראל

זקוק לעזרה?

  • בורר מוצרים

    חפשו ברשת של מפיצים מאומתים עם יותר מ-15,000 שקעי למכירה ברחבי העולם.

  • קבלת הצעת מחיר

    התחילו את בקשת הקניה בצורה מקוונת ונציג מכירות ייצור עמכם קשר.

  • היכן לקנות?

    אתר בקלות את מפיץ Schneider Electric הקרוב ביותר אליך.

  • מרכז העזרה

    חפשו משאבי תמיכה לכל הצרכים שלכם במקום אחד.

  • תיעוד מוצרים
  • בורר המוצר
  • מוצרים חלופיים והחלפה
  • מרכז עזרה ויצירת קשר
  • איתור סניפי שניידר אלקטריק
  • היכן לקנות
  • משרות
  • פרופיל חברה
  • דיווח על התנהגות בלתי הולמת
  • נגישות
  • חדר חדשות
  • משקיעים
  • EcoStruxure
  • חיפוש משימה
  • בלוג
  • מדיניות שמירה על פרטיות
  • הודעה על קובצי Cookie
  • תנאי שימוש
  • Change your cookie settings