PDPM288G6H: Install Manual Requires 4-wire Input. Is 3-Wire Acceptable?
Issue:
The installation manual requires a 4-Wire (3 phases + Neutral + PE) for the input and output. This PDU has a transformer in it. Can it be installed as a 3-Wire (3 phases + PE) on the input with the transformer creating a Neutral on the output for the load?
Product line:
Modular PDU
Environment:
All models, all serial numbers
Cause:
Customer requested information since 4-wire wasn’t available in the installation location. The installation manual, one-line diagrams, and the service manual do not provide specification as to why 4-wire is required.

Resolution:
No, this PDU requires 4-wire on the input and output.
The input neutral is required since it is the same neutral used for the output. The Auto Transformer doesn’t have a Star Point to create a the neutral needed by the load.

The installation manual requires a 4-Wire (3 phases + Neutral + PE) for the input and output. This PDU has a transformer in it. Can it be installed as a 3-Wire (3 phases + PE) on the input with the transformer creating a Neutral on the output for the load?
Product line:
Modular PDU
Environment:
All models, all serial numbers
Cause:
Customer requested information since 4-wire wasn’t available in the installation location. The installation manual, one-line diagrams, and the service manual do not provide specification as to why 4-wire is required.
Resolution:
No, this PDU requires 4-wire on the input and output.
The input neutral is required since it is the same neutral used for the output. The Auto Transformer doesn’t have a Star Point to create a the neutral needed by the load.
פורסם עבור: שניידר אלקטריק ישראל
זקוק לעזרה?
בורר מוצרים
חפשו ברשת מפיצים מאומתים עם יותר מ-15,000 נקודות מכירה ברחבי העולם.
קבלת הצעת מחיר
התחילו את בקשת הקניה בצורה מקוונת ונציג מכירות ייצור עמכם קשר.
היכן לקנות?
אתר בקלות את מפיץ Schneider Electric הקרוב ביותר אליך.
מרכז העזרה
חפשו משאבי תמיכה לכל הצרכים שלכם במקום אחד.