IEC 60870-5-101 Communication Protocol on PowerLogic P5 Protection Relays
Issue:
How to configure and use IEC 60870-5-101 protocol for PowerLogic P5 relays, including supported features, data mapping, and integration requirements.
Product:
PowerLogic P5 Protection Relay
Environment:
SCADA systems using IEC 60870-5-101 over serial RS-485 or fiber optic
Industrial automation networks requiring standardized telecontrol
Configuration tools: eSetup Easergy Pro, Web HMI
Cause:
IEC 60870-5-101 is a widely used protocol for telecontrol and event reporting in substations. Incorrect configuration of addressing, scaling, or control parameters can lead to communication failures, missing events, or improper control execution.
Resolution:
- Protocol Support:
- Serial communication only (RS-485 or fiber)
- Configurable via COMMUNICATION menu or eSetup Easergy Pro/Web HMI
- Device reboot required after protocol changes
- Data Model:
- Supports 64 Single Point Information (SPI), 32 Double Point Information (DPI), 32 Analog Inputs (AI), 16 Accumulated Energy (AE), 16 Integrated Totals (IT), and 8 Command objects
- Extensive mapping for protection, measurement, control, alarms, counters, and settings
- Functions Supported:
- Overcurrent (I>1–6), earth fault (IN>1–6), voltage (V>1–3, V<1–3), frequency (f>1–8, f<1–8), df/dt, differential, inrush, arc, motor, feeder, CB fail, synchro-check, fault locator
- Control Capabilities:
- Open/Close, Select/Execute for up to 6 objects
- Setting group change, clear min/max/demand, latch release
- Event Reporting:
- 250-event buffer with detailed event codes for protection, CB, arc, RTD, GOOSE, and environmental conditions
- Communication Parameters:
- Bit rate: 1200–115200 bps
- Link address: 1–254; ASDU address: up to 65534
- Supports 2/3-byte IO addressing, time tagging, and deadband configuration
- Security:
- No encryption; use network segmentation, firewalls, and IP whitelisting
- Protocol access configurable as read-only or read-write
- Integration:
- Fully documented mapping tables for SCADA integration
- Scaling examples: 1.00 pu = 100, 50.00 Hz = 5000
פורסם עבור: שניידר אלקטריק ישראל
זקוק לעזרה?
בורר מוצרים
חפשו ברשת מפיצים מאומתים עם יותר מ-15,000 נקודות מכירה ברחבי העולם.
קבלת הצעת מחיר
התחילו את בקשת הקניה בצורה מקוונת ונציג מכירות ייצור עמכם קשר.
היכן לקנות?
אתר בקלות את מפיץ Schneider Electric הקרוב ביותר אליך.
מרכז העזרה
חפשו משאבי תמיכה לכל הצרכים שלכם במקום אחד.