Firmware Upgrade Procedure for Sage RTU
Issue:
How to upgrade firmware on Sage RTU devices securely and correctly.
Product:
Schneider Electric Sage RTU Series (SAGE 1X10, 1X30, 1X50, 2X00, 3030X)
Environment:
- Sage RTU running secure firmware
- Windows PC with Internet Explorer or Chrome
- Firmware update package (C3414-500-S02YZ_Firmware_Update.zip)
- Microsoft .NET Framework 3.5 or later
- Direct Ethernet or PPP connection
Cause:
Firmware upgrades are needed for security patches, feature enhancements, and compliance. Incorrect steps can cause configuration loss or RTU crash recovery mode.
Resolution:
Step 1. Preparation.
1.1- Backup current configuration via GUI (Up/Download tab → Get from RTU).
1.2.-Download firmware update zip (available Here) and extract tools: Config Converter and User Manager.
1.3.-Use Config Converter to update configuration to match new firmware revision.
1.4.-Use User Manager to create/update user package with roles and SSH keys.
Step 2. Upgrade Steps:
2.1.-Log in to RTU GUI with Up/Download privilege.
2.2.-Go to Up/Download tab.
2.3.- Upload files in order:
-
- Firmware: C3414-500-S02YZ_firmware.tar.gz
- Configuration: C3414-500-S02YZ_config.tar.gz
- User Info: Desc_Ver_Users.tar.gz
2.4.-Click Send to RTU.
2.5.- Perform Normal Reset and wait ~60 seconds.
2.6.- Verify firmware version under CPU Configuration.
Notes:
- The system will prompt for a reboot, as is required after uploading new configuration files.
- Enable SSH/HTTPS for secure mode.
- If RTU enters Crash Recovery mode, upload safe configuration via console.
פורסם עבור: שניידר אלקטריק ישראל
זקוק לעזרה?
בורר מוצרים
חפשו ברשת מפיצים מאומתים עם יותר מ-15,000 נקודות מכירה ברחבי העולם.
קבלת הצעת מחיר
התחילו את בקשת הקניה בצורה מקוונת ונציג מכירות ייצור עמכם קשר.
היכן לקנות?
אתר בקלות את מפיץ Schneider Electric הקרוב ביותר אליך.
מרכז העזרה
חפשו משאבי תמיכה לכל הצרכים שלכם במקום אחד.