The ObF [Over Braking Fault] appears when the drive is in a run state and voltage on a DC bus is over the OBF level that represents 825V DC (a N4 version), When there is a voltage dip, the drive goes in the deceleration mode & if the motor is connect to high inertia load, it works in a Generator mode & trip on OBF fault.
Most usual cases of OBF fault are:
- Motor works in a Generator mode
- The braking is too dynamic
Both cases cause too much energy to dissipate in DC bus.
To avoid that:
- Increase the DEC [Deceleration ramp] as much as the application allows;
- Activate the brA[Dec ramp adapt.] parameter, IF APPLICATION ALLOWS. Not possible if the [BRAKE LOGIC CONTROL] function is active;
- Use a braking resistor
Most usual cases of OBF fault are:
- Motor works in a Generator mode
- The braking is too dynamic
Both cases cause too much energy to dissipate in DC bus.
To avoid that:
- Increase the DEC [Deceleration ramp] as much as the application allows;
- Activate the brA[Dec ramp adapt.] parameter, IF APPLICATION ALLOWS. Not possible if the [BRAKE LOGIC CONTROL] function is active;
- Use a braking resistor