{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
How can we help you today?
What is the Over Braking Fault on Altivar 61 drive.
The ObF [Over Braking Fault] appears when the drive is in a run state and voltage on a DC bus is over the OBF level that represents 825V DC (a N4 version), When there is a voltage dip, the drive goes in the deceleration mode & if the motor is connect to high inertia load, it works in a Generator mode & trip on OBF fault.

Most usual cases of OBF fault are:
- Motor works in a Generator mode
- The braking is too dynamic

Both cases cause too much energy to dissipate in DC bus.

To avoid that:
- Increase the DEC [Deceleration ramp] as much as the application allows;
- Activate the brA[Dec ramp adapt.] parameter, IF APPLICATION ALLOWS. Not possible if the [BRAKE LOGIC CONTROL] function is active;
- Use a braking resistor

Schneider Electric India

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: